Mersen Select-A-Fuse
Motors
3-phase LV
3-phase MV
1-phase LV
Type 2 protection
Transformers
3-phase LV
3-phase MV
1-phase LV (control)
Capacitors
3-phase LV
3-phase MV
General
Heating
Lighting
Other non-inductive
Coordination
LV fuses in series
E-rated MV in series
E-rated MV across transformer
E-rated MV to LV across transformer
E-rated MV to R-rated across transformer
E-rated to R-rated in series
Fuse Data
Overview of fuse types
Time-current curves
Peak let-thru data
Fuse outlines
Fuse blocks - overview
Fuse block outlines
PDBs
PDB selector
Finger-Safe PDB selector
PDBs - overview
PDB outlines
Finger-Safe PDBs - overview
Finger-Safe PDB outlines
Specs
AMP-TRAP 2000
General spec
Calculators
Quick Short Circuit Calculator
Arc Flash Calculator
Options
Results
Browse/edit
Delete
Help
Program Help
Protection Basics
Phone & Fax numbers - USA
Phone & Fax numbers - Canada
About Select-A-Fuse
File Browser
AMP-TRAP 2000 Suggested Fuse Specifications 1.0 General The electrical contractor shall furnish and install a complete set of fuses for all fusible equipment on the job as specified by the electrical drawings. Final tests and inspection shall be made prior to energizing the equipment. This shall include tightening all electrical connections and inspecting all ground conductors. Fuses shall be as follows: 2.0 Mains, Feeders and Branch Circuits A. Circuits 601 to 6000 amperes shall be protected by current-limiting Mersen Amp-Trap 2000 Class L time delay A4BQ fuses. Fuses shall be time delay and shall hold 500% of rated current for a minimum of 4 seconds, clear 20 times rated current in .01 seconds or less and be UL listed and CSA certified with an interrupting rating of 200,000 rms symmetrical amperes. B. Circuits 600 amperes or less shall be protected by current-limiting Mersen Smart Spot Amp-Trap 2000 Class RK1 time delay A2D (250V) or A6D (600V) or Class J time delay AJT fuses. Fuses shall hold 500% of rated current for a minimum of 10 seconds (30A, 250V Class RK1 case size shall be a minimum of 8 seconds) and shall be UL listed and CSA certified with an interrupting rating of 200,000 rms symmetrical amperes. C. Motor Protection All individual motor circuits shall be protected by Mersen Amp-Trap 2000 Class RK1, Class J, or Class L time delay fuses as follows: - For circuits up to 480A Class RK1 - A2D(250V) or A6D(600V) Class J - AJT - For circuits over 480A Class L - A4BQ Fuse sizes for motor protection shall be chosen from tables published by Mersen for the appropriate fuse. Heavy load and maximum fuse ratings are also shown for applications where typical ratings are not sufficient for the starting current of the motor. D. Motor Controllers Motor controllers shall be protected from short circuits by Mersen Smart Spot Amp-Trap 2000 time delay fuses. For Type 2 protection of motor controllers, fuses shall be chosen in accordance with motor control manufacturers' published recommendations, based on Type 2 test results. The fuses shall be Class RK1 A2D(250V) or A6D(600V) or Class J AJT or Class CC ATDR(600V). E. Circuit breakers and circuit breaker panels shall be protected by Mersen Smart Spot Amp-Trap 2000 fuses Class RK1 (A2D or A6D), Class J (AJT) or Class L (A4BQ) sized in accordance with tested UL Recognized Component Directory. In Canada circuit breakers shall be protected according to CEC Rule 14-014, Series Rated Combinations. F. Lighting and control circuits in the connected combinations shown up to 600Vac shall be protected by Mersen Amp-Trap2000 Class CC time delay ATDR or ATQR fuses, sized according to the electrical drawings. 3.0 Spares Spare fuses amounting to 10%(minimum three) of each type and rating shall be supplied by the electrical contractor. These shall be turned over to the owner upon project completion. Fuses shall be contained and cataloged within the appropriate number of spare fuse cabinets (no less than one), located per project drawings. Spare fuse cabinets shall be equipped with a key lock handle, be dedicated for storage of spare fuses and shall be ATFC, as supplied by Mersen. 4.0 Execution A. Fuses shall not be installed until equipment is to be energized. All fuses shall be of the same manufacturer to assure selective coordination. B. As installed drawings shall be submitted to the engineer after completion of the job. C. All fusible equipment rated 600 amperes or less shall be equipped with fuse clips to accept Class RK1 or Class J fuses as noted in the specifications. 5.0 Substitution Fuse sizes indicated on drawings are based on Mersen Amp-Trap 2000 fuse current-limiting performance and selectivity ratios. Alternative submittals to furnish materials other than those specified, shall be submitted to the engineer in writing two weeks prior to bid date, along with a short circuit and selective coordination study.
AMP-TRAP 2000 Suggested Fuse Specifications 1.0 General The electrical contractor shall furnish and install a complete set of fuses for all fusible equipment on the job as specified by the electrical drawings. Final tests and inspection shall be made prior to energizing the equipment. This shall include tightening all electrical connections and inspecting all ground conductors. Fuses shall be as follows: 2.0 Mains, Feeders and Branch Circuits A. Circuits 601 to 6000 amperes shall be protected by current-limiting Mersen Amp-Trap 2000 Class L time delay A4BQ fuses. Fuses shall be time delay and shall hold 500% of rated current for a minimum of 4 seconds, clear 20 times rated current in .01 seconds or less and be UL listed and CSA certified with an interrupting rating of 200,000 rms symmetrical amperes. B. Circuits 600 amperes or less shall be protected by current-limiting Mersen Smart Spot Amp-Trap 2000 Class RK1 time delay A2D (250V) or A6D (600V) or Class J time delay AJT fuses. Fuses shall hold 500% of rated current for a minimum of 10 seconds (30A, 250V Class RK1 case size shall be a minimum of 8 seconds) and shall be UL listed and CSA certified with an interrupting rating of 200,000 rms symmetrical amperes. C. Motor Protection All individual motor circuits shall be protected by Mersen Amp-Trap 2000 Class RK1, Class J, or Class L time delay fuses as follows: - For circuits up to 480A Class RK1 - A2D(250V) or A6D(600V) Class J - AJT - For circuits over 480A Class L - A4BQ Fuse sizes for motor protection shall be chosen from tables published by Mersen for the appropriate fuse. Heavy load and maximum fuse ratings are also shown for applications where typical ratings are not sufficient for the starting current of the motor. D. Motor Controllers Motor controllers shall be protected from short circuits by Mersen Smart Spot Amp-Trap 2000 time delay fuses. For Type 2 protection of motor controllers, fuses shall be chosen in accordance with motor control manufacturers' published recommendations, based on Type 2 test results. The fuses shall be Class RK1 A2D(250V) or A6D(600V) or Class J AJT or Class CC ATDR(600V). E. Circuit breakers and circuit breaker panels shall be protected by Mersen Smart Spot Amp-Trap 2000 fuses Class RK1 (A2D or A6D), Class J (AJT) or Class L (A4BQ) sized in accordance with tested UL Recognized Component Directory. In Canada circuit breakers shall be protected according to CEC Rule 14-014, Series Rated Combinations. F. Lighting and control circuits in the connected combinations shown up to 600Vac shall be protected by Mersen Amp-Trap2000 Class CC time delay ATDR or ATQR fuses, sized according to the electrical drawings. 3.0 Spares Spare fuses amounting to 10%(minimum three) of each type and rating shall be supplied by the electrical contractor. These shall be turned over to the owner upon project completion. Fuses shall be contained and cataloged within the appropriate number of spare fuse cabinets (no less than one), located per project drawings. Spare fuse cabinets shall be equipped with a key lock handle, be dedicated for storage of spare fuses and shall be ATFC, as supplied by Mersen. 4.0 Execution A. Fuses shall not be installed until equipment is to be energized. All fuses shall be of the same manufacturer to assure selective coordination. B. As installed drawings shall be submitted to the engineer after completion of the job. C. All fusible equipment rated 600 amperes or less shall be equipped with fuse clips to accept Class RK1 or Class J fuses as noted in the specifications. 5.0 Substitution Fuse sizes indicated on drawings are based on Mersen Amp-Trap 2000 fuse current-limiting performance and selectivity ratios. Alternative submittals to furnish materials other than those specified, shall be submitted to the engineer in writing two weeks prior to bid date, along with a short circuit and selective coordination study.